2017 Generac Guardian 3-Phase 20kW Automatic Model #7077

$4,399.00


Availability
Brochure
Year
2017
Manufacturer
Generac
Model
Guardian 3-Phase 20kW Automatic Model #7077

Overview

Description

One of the most powerful air-cooled generators on the market today, the Guardian Series 3-Phase 20 kW Standby Generator can provide whole-house backup power for many homes.

Features
  • 5 Year Limited Warranty for automatic standby generators.
  • True Power™ Technology delivers best-in-class power quality with less than 5 percent total harmonic distortion for clean, smooth operation of sensitive electronics and appliances.
  • Generac generators and engines are engineered and built in the USA*. *Built in the USA using domestic and foreign parts
  • Generac's G-Force Engine are purpose built, pressure-lubricated engine capable of handling the rigors of generator use, resulting in power that's more reliable and requires less routine maintenance than any other competitor.
  • 24/7/365 Customer Support Team standing by all day, every day from our headquarters in Wisconsin to answer any questions you might have.
  • Durable powder-coat finish helps make the sturdy, galvanneal steel enclosure perfect for all weather conditions
  • Smart, User-Friendly Controls Generac’s Evolution™ Controller features a dual-line, multilingual LCD display allowing for easy monitoring of history, maintenance logs making it easier to manage your generator.
  • Mobile Link™ Remote Monitoring allows you to monitor the status of your generator from anywhere in the world using a smartphone, tablet, or PC. Easily access information, such as the current operating status and the generator’s maintenance schedule. Connect your account to your authorized service dealer for fast, friendly and convenient assistance. (sold separately)
Specifications
  • Rated Maximum Continuous Power Capacity (LP): 20,000 Watts*
  • Rated Maximum Continuous Power Capacity (NG): 17,000 Watts*
  • Rated Voltage: 208
  • Rated Maximum Continuous Load Current – 208 Volts (LP/NG): 69.4/59.0
  • Total Harmonic Distortion: Less than 5%
  • Main Line Circuit Breaker: 80 Amp
  • Phase: 3
  • Number of Rotor Poles: 2
  • Rated AC Frequency: 60 Hz
  • Power Factor: .8
  • Battery Requirement (not included): Group 26R, 12 Volts and 540 CCA Minimum or Group 35AGM, 650 CCA Minimum
  • Unit Weight (lb/kg): 466/211
  • Dimensions (L x W x H) in/mm: 48 x 25 x 29/1218 x 638 x 732
  • Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load**: 67
  • Sound output in dB(A) at 23 ft (7 m) with generator in Quiet-Test™ low-speed exercise mode**: 58
  • Exercise Duration: 5 min.
Engine
  • Type of Engine: GENERAC G-Force 1000 Series
  • Number of Cylinders: 2
  • Displacement: 999 cc
  • Cylinder Block: Aluminum w/Cast Iron Sleeve
  • Valve Arrangement: Overhead Valve
  • Ignition System: Solid-state w/Magneto
  • Governor System: Electronic
  • Compression Ratio: 9.5:1
  • Starter: 12 Vdc
  • Oil Capacity Including Filter: Approx. 1.9 qt./1.8 L
  • Operating rpm: 3,600
  • Fuel Consumption: Natural Gas ft³/hr (m³/hr) 1/2 Load: 219 (6.20)
  • Fuel Consumption: Natural Gas ft³/hr (m³/hr) Full Load: 307 (8.69)
  • Fuel Consumption: Liquid Propane ft3/hr (gal/hr) [l/hr] 1/2 Load: 87 (2.39) [9.03]
  • Fuel Consumption: Liquid Propane ft3/hr (gal/hr) [l/hr] Full Load: 130 (3.56) [13.48]
NOTES:
Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet at all load ranges - 3.5-7" water column (7-13 mm mercury) for natural gas, 10-12" water column (19-22 mm mercury) for LP gas. For Btu content, multiply ft³/hr x 2500 (LP) or ft³/hr x 1000 (NG). For Megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG). **Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters. Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu/megajoule content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet (304.8 meters) above sea level; and also will decrease about 1 percent for each 6 °C (10 °F) above 16 °C (60 °F).

Specs

Engine

Engine Type
GENERAC G-Force 1000 Series
Displacement
999cc

Dimensions

Length
48 in. (1218 mm)
Width
25 in. (638 mm)
Height
29 in. (732 mm)
Weight
466 lb. (211 kg)

Other

AC Output
LP: 20,000 Watts; Natural Gas: 17,000 Watts
Noise Level
67 dB(A); Quiet-Test™: 58 dB(A)